Kohler generators and NH Electrician, electrical services for commercial and homes.
 

750 kW

Diesel Generators / 750REOZM

FeaturesSpecifications
  • Kohler Co. provides one-source responsibility for the generating system and accessories.
  • The generator set and its components are prototype-tested, factory-built, and production-tested.
  • The generator set accepts rated load in one step.
  • The 60 Hz generator set offers a UL 2200 listing (5M4036 and 5M4278 alternators only).
  • The generator set complies with ISO 8528-5, Class G3, requirements for transient performance.
  • A one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.

Alternator features:
  • The pilot-excited, permanent-magnet (PM) alternator provides superior short-circuit capability.
  • The brushless, rotating-field alternator has broad range reconnectability.
  • NEMA MG1 ,IEEE, and ANSI standards compliance for temperature rise and motor starting.
  • Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
  • Sustained short-circuit current enabling down stream circuit breakers to trip without collapsing the alternator field.
  • Self-ventilated and dripproof construction.
  • Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
  • Digital solid-state, volts-per-hertz voltage regulator with ±0.25% no-load to full-load regulation.
  • Brushless alternator with brushless pilot exciter for excellent load response.

Other features:
  • Controllers are available for all applications.
  • The low coolant level shutdown prevents overheating (standard on radiator models only).
FeaturesSpecifications
Prime Ratings: 690 kW (863 kVa)
Standby Ratings: 760 kW (950 kVa)
Hertz: 60 Hz
Alternator Type: Brushless, Permanent-Magnet Pilot Exciter
Engine Manufacturer: Mitsubishi
Engine Model: S12A2-Y1PTA-1
Cylinder Arrangement: 12-V
Max Power at Rated RPM: 900 kWm (1207 BHP)
Prime Fuel Consumption at
100% load: 199.1 Lph (52.6 gph)
75% load: 151.8 Lph (40.1 gph)
50% load: 112.4 Lph (29.7 gph)
25% load: 72.7 Lph (19.2 gph)
Standby Fuel Consumption at
100% load: 219.2 Lph (57.9 gph)
75% load: 165.8 Lph (43.8 gph)
50% load: 118.1 Lph (31.2 gph)
25% load: 77.6 Lph (20.5 gph)

Category: Diesel Generators / 750REOZM

 

750 kW Diesel Generators Industrial